Paint spray and powder coating processes

Many manufactured products are finished by the application of paint to the surface. Paint serves to protect the object from the elements and improves the appearance at the same time. This page examines paint spray and powder coating systems, emphasizing the physical hazards involved and the appropriate risk control measures to be taken. A discussion of health and safety hazards not related to fire and explosion is beyond the scope of this page.

Introduction

Paint, in one form or another, has been used for the protection and beautification of finished products and structures for thousands of years. Most paints are formulated as mixtures of three basic components — resinous or resin-forming "binder," pigment, and a solvent — and are applied as a coating to various types of surfaces. The purpose of the coating may be decorative, protective or functional.

Mechanical processes for the spray application of paint have evolved over the past hundred years. The first of these processes, known as the conventional paint spray process, uses air under pressure to atomize the paint by forcing it through a spray gun nozzle at low pressure. Since the paint spray guns are designed to handle only liquids of low viscosity, most of the paints used are diluted with solvents. Since the 1930s, several other spray finishing processes have been developed to overcome some of the shortcomings of the conventional spray process, such as viscosity of the paint, amount of solvent overspray, and excessive evaporation loss. These painting processes include the hot spray, vapor spray, airless or high-pressure spray and electrostatic spray processes. Of the four latter methods, the vapor spray process is rarely used.

The area where painting takes place is referred to as a spray area. Spray areas are locations where quantities of flammable or combustible vapors are present because of a spraying operation. They may be enclosed, unenclosed, or partially enclosed. Partially enclosed spray areas, such as spray hoods, are used in conjunction with ventilation systems. They are typically enclosed on three sides, fresh air is drawn through the fourth side across the spray area, and out through an exhaust system. Spray booths are fully enclosed areas within a larger room that contains the paint spray operations. Spray booths are ventilated to remove hazardous concentrations of vapors through an exhaust system. They provide additional protection by enclosing the space where flammable vapors could be concentrated.

This page will cover the fire and explosion hazards of the commonly used spray processes and provide information on the control measures recommended for each process. In addition, the report will cover the powder application of finishes, as related to these processes. However, NFPA 33, Standard for Spray Application Using Flammable or Combustible Materials, published by the National Fire Protection Association (NFPA) should be consulted for detailed requirements related to control of these hazards.

While this page provides, some basic information related to health hazards of paint application processes, a detailed analysis of the health hazards encountered is beyond the scope of this page. The risk control consultant or industrial hygienist should obtain a list of the materials used, before visiting a risk, so that possible health hazards can be considered.

Sprayed materials

The three major paint types in use are water-based, oil-based and powder paints. Water-based and oil-based paints contain a solvent for ease of dispersal. Dry powders, as used in the powder coating system, eliminate the solvent. The material is applied in a finely granulated, powder form, either to a heated surface or, as in the electrostatic spray process, to a cold surface that is then heated to form the smooth, finished coating. Powder coatings eliminate the problem related to the use of solvents and overspray, yet they do have their own inherent hazard because of the potential for a dust explosion.

Binders

Binders can be oils, such as alkyds, cellulosic, acrylics, vinyls, phenolics, epoxies, polyurethanes, silicones, and amino resins or latexes, such as styrene-butadiene polyvinyl acetates and acrylics.

Pigments

Pigments are divided into inorganic, such as whites (e.g., titanium dioxide, lithopone, etc.); extender (i.e., fillers), inert and supplemental pigments, such as calcium carbonate, clays, talcs and silicas; inorganic colors (e.g., iron oxides, red lead, chrome yellows and oranges, zinc yellow, etc.), blacks and metallics; and organic pigments, such as the insoluble azo pigments, acid azo pigments and phthalocyanines.

Solvents

Solvents may be either water or low-, medium- or high-boiling point solvents, such as hydrocarbons, alcohols, ethers, ketones, esters, chlorinates or nitrated solvents.

Spray processes

The conventional spray process is still widely used in industry, especially where there is a wide diversity of colors to be applied in a short span of time. Due to its inherent limitations, discussed below, it is gradually being replaced by the newer processes, such as hot spray, airless and electrostatic spraying. The plural component and powder coating systems are specialized systems that can be incorporated within any of the four major spray processes.

The main uses of the hot spray, airless and electrostatic spray processes are where high production, uniform coating, limited overspray and reduced solvent pollution are desired. They have found wide usage in the finishing of automobile, truck, and trailer bodies, prefabricated homes and automated or semi-automated paint spray operations. Increasingly, the airless method of paint application has found favor among large and small commercial paint contractors and among homeowners, in the case of small airless units.

Conventional spray process

Conventional spray guns use air pressure to atomize the paint by forcing it through a nozzle at low pressures of 60-70 psig (414-483 kPa) for industrial processing and as low as 40 psig (276 kpa) for commercial and home operations. The paint may be aerated before it leaves the nozzle, or it may be mixed and aerated in front of the nozzle depending on the type of paint and its application. Since the guns are designed to handle liquids of low viscosity, the paints are usually diluted with either water- or hydrocarbon-based solvents.

A major challenge of the conventional spray process, especially where large volumes of paint are prepared and used with hydrocarbon-based solvents, has been maintaining the paint at a constant viscosity. Batch mixing of these paints tends to cause inconsistency in the viscosity due to changing temperatures and solvent expansion. For example, paints thinned in the morning may be too thin later in the day due to increasing ambient temperatures. Another problem is that a fire and explosion hazard is created as the solvent is evaporated in the drying process. In addition, the air pressures required to atomize the thinned paint can cause considerable overspray of paint and solvents. This overspray is wasted by being deposited in the spray booth or exhausted to the atmosphere.

Hot spray process

In the hot spray process, the paint is heated and then discharged at lower atomizing air pressures, thereby resulting in less paint overspray. Due to the lowered viscosity, heavier paints using smaller amounts of solvent may be used. With smaller amounts of solvent and reduced air pressures, heavier coats of paint can be applied with each pass of the spray gun. The drying time is shortened, since less solvent is required, and the application of the hot paint causes the solvent to vaporize faster.

The equipment used is similar to that used in conventional spray painting except that the paint is heated to 140°F (60°C) to 180°F (82°C) to reduce its overall viscosity by one-third to one-fourth. The paint heater can be an electrical heater or a heat exchanger using hot water, steam or other hot liquids or gases. Paint heaters are usually self-contained units composed of a heater, a pump, a paint-filtering system and a supply tank.

Hot spray systems are mainly used where high-viscosity paints are required, where a heavy coat of paint is required per application, and where cost or other considerations do not require the switch to an airless spray system.

Airless (high pressure) spray process

In an airless or high-pressure spraying process, the paint is atomized by forcing it through specially designed nozzles at high fluid pressures, normally between 1,500 and 2,500 psig (10,342 and 17,237 kPa). In some systems, the pressures may run as low as 200 psig (1,379 kpa) and, in others, as high as 5,000 psig (34,475 kpa). A heating system for the paint can be used to control viscosity, decrease the amount of solvent and reduce the thickness of the applied film. Using a heater, the paint can be sprayed at lower hydraulic pressures, often as low as 200 psig (1,379 kpa). The equipment usually consists of an air-driven hydraulic pump, high-pressure paint hoses and special spray guns.

This process produces very little turbulence or rebound of the paint particles and minimal overspray. The savings in paint and solvent can be considerable when compared to the cost of using conventional spray processes.

Electrostatic paint processes

The electrostatic spray process and the drip-deterring paint process were developed during the 1930s. Both processes rapidly found widespread use in the mass production of painted products, such as automobile and truck bodies and household products. The electrostatic spray process and dip deterring of paint process operate on the basic law of physics that unlike electrical charges attract each other and like electrical charges repel. In both processes, a transformer-rectifier unit is used to convert 240 volts AC to 85,000-130,000 volts AC. This higher voltage is then converted through half-wave rectification to 60,000-91,000 volts DC. Then, depending on the process, either the paint or the object to be painted is provided with a negative charge and the other (paint or object) is grounded. Thus, the paint being fluid will move either toward the object as in the electrostatic spray process, or away as in the dip-deterring process.

Electrostatic spray process

In electrostatic spray painting, the paint can be atomized by air pressure to as low as 4-5 psig (28-35 kpa), or by the rapid rotation of bells or discs. When air pressure is used, the paint particles can be given the negative charge at the spray gun or by passing them adjacent to or through a grid held at high voltage. The paint particles are charged by the grid and thus propelled to the work that has an opposite electrical charge. If rotating bells or discs are used to atomize the paint, the particles are given the negative electrical charge at the edge of the bells or discs.

Either the spray guns or rotating bells or discs used may be fixed, with the work passing in front or around them, or they may be portable. The operation is the same for both. The portable guns are mainly used for small runs or differently shaped objects, or where mass production dictates the mixing of different products on the same line. Because the negatively charged paint particles are attracted to all parts of the oppositely charged object, all sides of the object receive a uniform coating of paint when the guns are located properly. There is also little overspray, resulting in substantial savings of paint and solvent.

Electrostatic dip process

The electrostatic process is reversed when objects are being dip-coated. The product, hung on work hooks attached to an overhead conveyor, is dipped in a paint dip tank or flow-coated, allowed to drain until the flow of paint has practically stopped and then carried over a negatively-charged deterring grid, usually charged at about 85,000 volts DC. An electrical attractive force is established between the electrostatic grid and the grounded article. This causes the "drips" or "tears" on the article to be attracted to the grid and results in a more uniform coating of paint.

Plural component systems

Plural component systems are mainly used for the application of organic peroxides, urethanes (including foamed and liquid types), epoxies and similar materials. In the modified version of the conventional spray process, the gun has two or more component lines, in addition to an air pressure hose. The plural component system can also be adapted to the hot-spray and airless paint processes. The components may be internally mixed in the gun, such as with foam-type materials, or blended externally, such as with the polyester and epoxy resin systems. The pressures used will vary with the type of process and system in use.

Plural component systems that use peroxides require special application equipment. The amount of peroxide used depends on the type and its end use. The peroxide delivery lines should be kept separate from all other delivery lines to reduce the possibility of fire and explosion.

Powder coating systems

"Powder dusting" is the oldest of the powder coating systems. An early example is the porcelainized finish found on sinks, bathtubs, washing machines, etc. In the process, the product is heated and then passed in front of a spray gun that flocks or dusts it. The product may or may not be returned to an oven to set the finish. The gun used usually has four or more controls to vary the amount of powder applied to the product.

"Fluidized bed process" is a method of expanding a powdered plastic material by passing an air stream through the material. The heated product is then lowered into the "bed" of material, withdrawn and then reheated, if necessary, to produce the desired resulting film. The thickness of the final coat to be applied is dependent on the temperature of the product, particle size and length of time the product remains in the "bed."

Electrostatic powder coating processes

In the electrostatic powder coating process, which is gradually replacing the older powder coating process, the product to be coated does not have to be heated and, as in all electrostatic systems, the applied coating can be of uniform thickness regardless of the complexity of the shape of the product. In these processes, the product to be coated is given an opposite charge from the powder.

The "electrostatic fluidized bed" differs from the "fluidized bed process" in that the "bed" is charged. The product to be coated is passed through the "bed" while it is under constant aeration. The powder, in the form of a fine dust, settles on the charged product in a uniform coat. The length of time within the dust cloud determines the thickness of the coat. Some systems, such as the in-line cascading fluidized bed, use two parallel-fluidized beds, with a wall partly separating each "bed" from a central area. The powders from the two beds intermix, forming a very fine dust that completely encloses the product. The thickness of the coating is determined by the length of the tunnel and the length of time the product remains in the tunnel.

The curtain and tunnel coating systems also use electrostatics to attract the paint to the product to be coated. The curtain coater uses a porous conveyer belt passing in front of the product to be coated. The belt picks up the powder that is then blown past a wire, charging the particles of powder, onto the oppositely charged product. The powder-coating tunnel introduces the product to be coated into a tunnel containing powder under constant aeration. The length of time for the passage of the product will determine the thickness of the coating.

Spray processes

The conventional spray process is still widely used in industry, especially where there is a wide diversity of colors to be applied in a short span of time. Due to its inherent limitations, discussed below, it is gradually being replaced by the newer processes, such as hot spray, airless and electrostatic spraying. The plural component and powder coating systems are specialized systems that can be incorporated within any of the four major spray processes.

The main uses of the hot spray, airless and electrostatic spray processes are where high production, uniform coating, limited overspray and reduced solvent pollution are desired. They have found wide usage in the finishing of automobile, truck, and trailer bodies, prefabricated homes and automated or semi-automated paint spray operations. Increasingly, the airless method of paint application has found favor among large and small commercial paint contractors and among homeowners, in the case of small airless units.

Conventional spray process

Conventional spray guns use air pressure to atomize the paint by forcing it through a nozzle at low pressures of 60-70 psig (414-483 kPa) for industrial processing and as low as 40 psig (276 kpa) for commercial and home operations. The paint may be aerated before it leaves the nozzle, or it may be mixed and aerated in front of the nozzle depending on the type of paint and its application. Since the guns are designed to handle liquids of low viscosity, the paints are usually diluted with either water- or hydrocarbon-based solvents.

A major challenge of the conventional spray process, especially where large volumes of paint are prepared and used with hydrocarbon-based solvents, has been maintaining the paint at a constant viscosity. Batch mixing of these paints tends to cause inconsistency in the viscosity due to changing temperatures and solvent expansion. For example, paints thinned in the morning may be too thin later in the day due to increasing ambient temperatures. Another problem is that a fire and explosion hazard is created as the solvent is evaporated in the drying process. In addition, the air pressures required to atomize the thinned paint can cause considerable overspray of paint and solvents. This overspray is wasted by being deposited in the spray booth or exhausted to the atmosphere.

Hot spray process

In the hot spray process, the paint is heated and then discharged at lower atomizing air pressures, thereby resulting in less paint overspray. Due to the lowered viscosity, heavier paints using smaller amounts of solvent may be used. With smaller amounts of solvent and reduced air pressures, heavier coats of paint can be applied with each pass of the spray gun. The drying time is shortened, since less solvent is required, and the application of the hot paint causes the solvent to vaporize faster.

The equipment used is similar to that used in conventional spray painting except that the paint is heated to 140°F (60°C) to 180°F (82°C) to reduce its overall viscosity by one-third to one-fourth. The paint heater can be an electrical heater or a heat exchanger using hot water, steam or other hot liquids or gases. Paint heaters are usually self-contained units composed of a heater, a pump, a paint-filtering system and a supply tank.

Hot spray systems are mainly used where high-viscosity paints are required, where a heavy coat of paint is required per application, and where cost or other considerations do not require the switch to an airless spray system.

Airless (high pressure) spray process

In an airless or high-pressure spraying process, the paint is atomized by forcing it through specially designed nozzles at high fluid pressures, normally between 1,500 and 2,500 psig (10,342 and 17,237 kPa). In some systems, the pressures may run as low as 200 psig (1,379 kpa) and, in others, as high as 5,000 psig (34,475 kpa). A heating system for the paint can be used to control viscosity, decrease the amount of solvent and reduce the thickness of the applied film. Using a heater, the paint can be sprayed at lower hydraulic pressures, often as low as 200 psig (1,379 kpa). The equipment usually consists of an air-driven hydraulic pump, high-pressure paint hoses and special spray guns.

This process produces very little turbulence or rebound of the paint particles and minimal overspray. The savings in paint and solvent can be considerable when compared to the cost of using conventional spray processes.

Electrostatic paint processes

The electrostatic spray process and the drip-deterring paint process were developed during the 1930s. Both processes rapidly found widespread use in the mass production of painted products, such as automobile and truck bodies and household products. The electrostatic spray process and dip deterring of paint process operate on the basic law of physics that unlike electrical charges attract each other and like electrical charges repel. In both processes, a transformer-rectifier unit is used to convert 240 volts AC to 85,000-130,000 volts AC. This higher voltage is then converted through half-wave rectification to 60,000-91,000 volts DC. Then, depending on the process, either the paint or the object to be painted is provided with a negative charge and the other (paint or object) is grounded. Thus, the paint being fluid will move either toward the object as in the electrostatic spray process, or away as in the dip-deterring process.

Electrostatic spray process

In electrostatic spray painting, the paint can be atomized by air pressure to as low as 4-5 psig (28-35 kpa), or by the rapid rotation of bells or discs. When air pressure is used, the paint particles can be given the negative charge at the spray gun or by passing them adjacent to or through a grid held at high voltage. The paint particles are charged by the grid and thus propelled to the work that has an opposite electrical charge. If rotating bells or discs are used to atomize the paint, the particles are given the negative electrical charge at the edge of the bells or discs.

Either the spray guns or rotating bells or discs used may be fixed, with the work passing in front or around them, or they may be portable. The operation is the same for both. The portable guns are mainly used for small runs or differently shaped objects, or where mass production dictates the mixing of different products on the same line. Because the negatively charged paint particles are attracted to all parts of the oppositely charged object, all sides of the object receive a uniform coating of paint when the guns are located properly. There is also little overspray, resulting in substantial savings of paint and solvent.

Electrostatic dip process

The electrostatic process is reversed when objects are being dip-coated. The product, hung on work hooks attached to an overhead conveyor, is dipped in a paint dip tank or flow-coated, allowed to drain until the flow of paint has practically stopped and then carried over a negatively-charged deterring grid, usually charged at about 85,000 volts DC. An electrical attractive force is established between the electrostatic grid and the grounded article. This causes the "drips" or "tears" on the article to be attracted to the grid and results in a more uniform coating of paint.

Plural component systems

Plural component systems are mainly used for the application of organic peroxides, urethanes (including foamed and liquid types), epoxies and similar materials. In the modified version of the conventional spray process, the gun has two or more component lines, in addition to an air pressure hose. The plural component system can also be adapted to the hot-spray and airless paint processes. The components may be internally mixed in the gun, such as with foam-type materials, or blended externally, such as with the polyester and epoxy resin systems. The pressures used will vary with the type of process and system in use.

Plural component systems that use peroxides require special application equipment. The amount of peroxide used depends on the type and its end use. The peroxide delivery lines should be kept separate from all other delivery lines to reduce the possibility of fire and explosion.

Powder coating systems

"Powder dusting" is the oldest of the powder coating systems. An early example is the porcelainized finish found on sinks, bathtubs, washing machines, etc. In the process, the product is heated and then passed in front of a spray gun that flocks or dusts it. The product may or may not be returned to an oven to set the finish. The gun used usually has four or more controls to vary the amount of powder applied to the product.

"Fluidized bed process" is a method of expanding a powdered plastic material by passing an air stream through the material. The heated product is then lowered into the "bed" of material, withdrawn and then reheated, if necessary, to produce the desired resulting film. The thickness of the final coat to be applied is dependent on the temperature of the product, particle size and length of time the product remains in the "bed."

Electrostatic powder coating processes

In the electrostatic powder coating process, which is gradually replacing the older powder coating process, the product to be coated does not have to be heated and, as in all electrostatic systems, the applied coating can be of uniform thickness regardless of the complexity of the shape of the product. In these processes, the product to be coated is given an opposite charge from the powder.

The "electrostatic fluidized bed" differs from the "fluidized bed process" in that the "bed" is charged. The product to be coated is passed through the "bed" while it is under constant aeration. The powder, in the form of a fine dust, settles on the charged product in a uniform coat. The length of time within the dust cloud determines the thickness of the coat. Some systems, such as the in-line cascading fluidized bed, use two parallel-fluidized beds, with a wall partly separating each "bed" from a central area. The powders from the two beds intermix, forming a very fine dust that completely encloses the product. The thickness of the coating is determined by the length of the tunnel and the length of time the product remains in the tunnel.

The curtain and tunnel coating systems also use electrostatics to attract the paint to the product to be coated. The curtain coater uses a porous conveyer belt passing in front of the product to be coated. The belt picks up the powder that is then blown past a wire, charging the particles of powder, onto the oppositely charged product. The powder-coating tunnel introduces the product to be coated into a tunnel containing powder under constant aeration. The length of time for the passage of the product will determine the thickness of the coating.

Drying processes

In addition to open air-drying, including the use heat lamps, ovens that may be used in the drying process may consist of direct-fired or indirect-fired heating units burning gas or oil or may make use of electrical heating, either using exposed electrical heaters or enclosed units, such as heating plates and lamps. These areas are referred to as "flash-off areas." The drying process may range from single-stage drying to more complicated processes that involve two or more drying stages, depending on the type of painting process in use. Additionally:

  • Flash-off areas that are heated above ambient temperatures should meet the requirements of NFPA 86, Standard for Ovens and Furnaces.
  • The heating or drying process, for flammable or explosive materials, should be restricted to ovens that add sufficient ventilation to the drying process to keep the concentration of flammables below 25 percent of their lower flammable or explosive limits.
  • Air circulation through these ovens must be distributed as uniformly as possible and with sufficient turbulence to ensure that the flammable vapor concentration in all parts of the oven is safely below the lower explosive limit (LEL) at all times.
  • Enclosed flash-off areas should be provided with an automatic fire protection system.

Fire and explosion hazards

The major physical hazards in any spray painting operation are fire and explosion. This arises from the materials used and the conditions of use. The following information covers some of the typical fire and explosion hazards related to each of the paint spraying processes.

Conventional spray process

Except for water-based paints, paint spraying processes use solvents that are flammable or combustible. The solvents include methanol, acetone, mineral spirits, styrene, methyl ethyl ketone (MEK), turpentine, toluene, xylene, and chlorinated hydrocarbons. Except for a few chlorinated hydrocarbons, most solvents have specific gravities less than water, low flash points and an explosion potential in normal spray operation concentrations, by volume, in air.

Additionally, paint buildup from overspray and spillage in paint hoods, on filters, within the ventilation systems, and in the surrounding areas can be a source of fires and explosions. A spark from operating equipment, or other sources of ignition, can cause a flash of fire through these areas, causing extensive damage. Spontaneous ignition may occur if the area is not kept free of paint and clear of organic wastes (e.g., rags, cloths, etc.). Spontaneous ignition may also occur if residues from two or more types of coatings are permitted to accumulate one on top of the other in the spray booth, exhaust duct, and filters.

Hot spray process

In addition to the fire and explosion hazards discussed above, the hot-spray process introduces the added factor of heat. The paint is heated by an electrical heater or a heat exchanger, using hot water, steam, or other hot liquids or gases. If there is a short in the electrical system, or if the wrong wiring is used, an explosion and fire may occur. Although there is less overspray with hot-spray processing, some solvent vapors will present a significant hazard at room temperature. Others, such as the chlorinated hydrocarbons, may not ignite at room temperatures, but can ignite at the temperatures used in the process [140°F (60°C) to 180°F (82°C)].

Airless spraying

In addition to the hazards previously discussed, there is a potential to generate a static spark during airless spraying, which can initiate a fire or an explosion. Additionally, if a high-pressure hose, normally between 1,500 (10,342 kPa) and 2,500 psig (17,237 kPa) is cut or punctured, highly volatile and explosive vapors can be released into the area. This can set the stage for an explosion of the materials should an ignition source be present.

Electrostatic paint processes

The electrostatic spray process and, to a lesser extent, the dip process introduce the possibility of a high-voltage electrical spark in an area of explosive vapors. The hazard mainly arises during the startup operation, especially after a changeover, when one color of paint or paint system is changed to another. During this period, the apparatus is thoroughly cleaned with solvent. If the solvent vapors are not removed by ventilation, or if spills are not cleaned up prior to the startup, an electrical spark may ignite the explosive vapors.

Plural component systems

The organic peroxides used in plural component systems are a high-hazard group of chemicals used as catalysts in the plastic and related industries. As a paint component, they should be considered as "potentially explosive chemicals" that can support combustion and can explode even though air is excluded from the process. Organic peroxides burn more rapidly than ordinary flammable liquids or combustible solids. An important factor that can accelerate the rate of decomposition of organic peroxides is heat. This may evolve as a slow and gradual increase in temperature, a very rapid and violent decomposition or an explosion.

Other factors of concern are decomposition vapors, contamination and liquids used to dilute the peroxide concentration. Some of the peroxides, on decomposing, will give off highly flammable gases and vapors, increasing the potential for a fire or explosion. Contamination with various materials, such as strong acids or bases, sulfur compounds, amines, accelerators or reducing agents of any type, will markedly reduce the stability of organic peroxides. The physical separation of very sensitive organic peroxides from their diluents can concentrate the shock-sensitive organic peroxides.

Because of these hazards, many companies have switched to epoxy- or isocyanate-based plural component systems, which present a much lesser fire hazard.

Powder coating systems

While most of the fire and explosion hazards previously discussed apply to the powder coatings process, as well, the primary hazard in this process is a dust explosion. This explosion hazard is increased in powdered coating processes when the powdered paint is dispersed in the air as a "fluidized" material or is sprayed onto the item being coated. Measurements have shown that the minimum explosive concentration of the powders used is approximately 0.02 oz./ft.3 (20 g/m3) of air. When this value is exceeded, such as when the concentration of recirculated exhaust air has not been reduced to an acceptable safe level, an explosion may occur.

Other causes of fires and explosions are related to the process itself and to the drying and cleaning of finished products. If the temperature of the product to be coated exceeds the ignition temperature of the coating, a fire and/or an explosion can occur. Fires and explosions can also occur during the cleaning of products and during plant cleanup operations through to the use of spray guns, which place solvents into airborne concentrations, rather than vacuum sweeping equipment.

Drying processes

The main hazard that arises during the drying process is explosion. Explosions in the drying oven can occur when the automatic controls used to monitor gas- and oil-fired ovens fail to prevent a buildup of combustible gas concentrations.

Risk control

The most important risk control considerations in paint spraying operations are the prevention of fire and explosion and control of health hazards, which is beyond the scope of this report. This may be accomplished by incorporating safety features into the paint spray system, segregating the paint spraying area, and training equipment operators.

The paint spraying areas should be designed, operated, and maintained in accordance with the requirements of NFPA 33, Standard for Spray Application Using Flammable or Combustible Materials, published by the National Fire Protection Association (NFPA). However, NFPA 33 does not provide information related to "hazards of toxicity or industrial health and hygiene," and such health hazards are beyond the scope of this report.

Conventional spray process

The basic fire protection measures for conventional spray process are also appropriate for all the other paint processes.

Spray areas

NFPA 33 provides requirements for the construction of spray areas, including, but not limited to:

  • Aluminum should not be used for structural support members or the walls or ceiling of an area, or in ventilation ductwork.
  • Paint spraying operations should be in an area specially designed for this purpose, protected with an approved system of automatic sprinklers, and separated from other areas by walls, floors and ceilings having a minimum of a one-hour fire-resistance rating.
  • Paint spraying operations located in assembly, educational, institutional or residual occupancies, protected with an approved system of automatic sprinklers and separated from other areas by walls, floors and ceilings having a minimum of a two-hour fire-resistance rating.
  • Paint spray booths should be separated from other areas by at least 3 ft. (0.9 m). Additional separation requirements are necessary for open-spray areas, spray hoods and spray rooms based on the degree of hazard present.

Electrical

  • Lighting fixtures should be listed/approved for use in hazardous areas and so located to prevent accumulation of overspray. Lighting equipment should be effectively isolated from the spray area by glass panels or other transparent materials, should be made of non-combustible materials and should be protected so that breakage will be unlikely.

Electrical equipment and wiring located in spray areas should be designed, installed, and approved in accordance with the provisions of NFPA 70, National Electrical Code, based on the type of hazard present (i.e., Class I, Division I). See Client Handout CH-25-22, Electrical Equipment - Hazardous Location Classification System, for additional information on hazardous electrical locations.

See Chapter 6 of NFPA 33 for specific electrical requirements for spray areas.

Ventilation

  • Mechanical ventilation should be provided for all spraying areas to remove flammable vapors, mists or powders, in accordance with NFPA 33. Fans and other related equipment should be constructed of non-ferrous metals to reduce the hazards of fire and explosion.
  • The paint spraying equipment and the ventilation system should be properly maintained.

See Chapter 7 of NFPA 33 for specific ventilation requirements for spray areas.

Operations

  • All paint spraying and surrounding areas should be kept free of the accumulation of deposits of combustible residues. Floor runners and similar coverings should be changed at least daily to prevent the buildup of combustible residues.
  • The storage and handling of flammable and combustible liquids should be in accordance with NFPA 30, Flammable and Combustible Liquids Code, as well as applicable federal, state, and local regulations.
  • "No Smoking" signs should be installed in all areas where flammable liquids and combustible dusts are used.

See Chapter 10 of NFPA 33 for additional requirements.

Protection

  • Paint spraying areas should be protected by an automatic suppression system, such as automatic sprinklers, carbon dioxide, dry chemical or clean agent systems.
  • Sprinkler heads in spray areas should be protected from overspray by either location or covering the head. Sprinkler heads may be covered with a "cellophane bag having a thickness of 0.08 mm (0.003 in) or less" or by thin paper bags. Such protective coverings should be "replaced frequently so that heavy deposits of residue do not accumulate."
  • Fire protection systems in continuous spray operations should be interlocked with the spray process, so that ion activation of the system, the spray process, is stopped and associated facility alarms are initiated.

See Chapter 9 of NFPA 33 for more details on specific fire protection requirements for spray operations.

Hot spray process

Risk control measures, in addition to the previous controls, for the hot spray processes include:

  • Paint heaters should be provided with thermostatic controls and a temperature gauge.
  • The paint container, heating jacket, and the pump discharge should be provided with pressure-relief valves.
  • Electric heaters should be listed/approved for the specific location in which they are used.
  • Heaters should not be in the spray booths, nor in any other location subject to the accumulation of deposits of combustible residue.
  • If agitators are used, they should be driven by compressed air, water, low-pressure steam or electricity. If electrically driven, the motor should conform to the requirements of the NFPA 70.
  • Hose lines should be designed for the pressures and temperatures used in the hot spray process.

Airless (high pressure) spray process

The hazard of airless spray process is related to the high pressure used. The following control measures, in addition to the controls for conventional spray processes, should be considered for both fixed- and hand-spraying equipment:

  • Pumps, tanks, paint hoses, fittings, paint guns and nozzles should be designed for the pressures required in the operation.
  • The pressure pump should be designed to stop the pump if the discharge pressure exceeds the safe operating pressure of the system.
  • High-pressure hoses should be designed for the pressures required, periodically inspected, and properly maintained. The hose should not be kinked or bent in less than the recommended radius stated by the manufacturer.
  • Hoses showing material deterioration, signs of leakage or weakness in the couplings should be withdrawn from service and repaired or discarded.
  • Airless high-pressure spray guns and the conductive object being sprayed should be electrically bonded together or connected to a common ground.
  • The spray gun should incorporate a safety diffuser to reduce the velocity and impact of the paint stream. An automatic check valve or lock should be incorporated in the gun to prevent a high-pressure jet of paint from being released if the gun is triggered while the nozzle is removed.
  • The spray nozzle should not be removed from the spray gun, nor disconnected from the paint hose, without first releasing the fluid pressure. The spray gun should not be pointed at any part of the body.
  • Approved safety glasses or goggles and approved gloves should be worn while in the spraying area.
  • Operators should be trained in the hazards of high-pressure or airless spray process, as well as procedures to follow in the event of an accident.
  • Safety warning information is recommended to be affixed or applied to the paint pump. The information should include:
  • Warning — High-Pressure Device. This equipment can cause serious injury. Do not alter equipment. Do not grab front end of gun or permit any part of the body to come near the face of the spray cap or tip. Use only conductive airless spray hose. When gun is not in use, always set safety lock in closed position. Read Instruction Manual carefully before operation. Maximum working pressure of spray gun is [_______] psi ([_______] kPa).

Electrostatic paint process

The introduction of high-voltage electricity into a volatile and explosive atmosphere warrants, in addition to the controls for conventional spray processes, the following control measures:

  • Transformers, power packs, control apparatus and all other electrical portions of the equipment, except for high-voltage grids and electrostatic atomizing heads and their connections, should be located outside the spraying area, unless otherwise specified.
  • The electrostatic apparatus should be equipped with automatic controls to disconnect the power supply to the high-voltage transformer and to signal the operator if the ventilation equipment fails, the conveyor or product line stops, or if an excessive voltage drop is detected.
  • High voltage leads to electrodes, and electrostatic atomizing heads should be effectively and permanently supported on suitable insulators and should be effectively guarded against accidental contact or grounding. Electrodes and insulators should be kept clean and dry.
  • An automatic means should be provided for grounding and discharging any accumulated residual charge on the electrode assembly or the secondary circuit of the high-voltage transformer when the transformer primary is disconnected from the source of supply.
  • The space maintained between the articles being painted and electrodes or atomizing heads should be at least twice the sparking distance. (A sign should be posted, designating the sparking distance for each installation.) The articles should be supported on conveyors that are arranged to maintain the safe distance at all times.
  • The spraying area should be adequately ventilated to minimize the possibility of explosion, fire and health hazards.
  • Adequate booths, fencing, railings, or guards should be placed about the equipment for the protection of personnel. These should be of conducting material and adequately bonded and grounded. They should be at least 5 ft. (1.5 m) from the processing equipment.
  • If electrically-conductive paint is used, the support unit and tank lines for the paint tank should be barricaded so that personnel will not be exposed to high voltage.
  • Employees should not be allowed to work on the electrostatic equipment while the current is on. Fail-safe photoelectric or body capacitance safety controls, or their equivalent, should be installed so that the power supply will shut off if a person approaches the equipment while it is operating.
  • A red signal warning lamp should be conspicuously mounted on the spray booth to indicate when the high voltage is on.

Electrostatic hand spraying

The use of electrostatic hand spraying equipment requires that, in addition to the controls for conventional spray processes, the following control measures be used:

  • Electrostatic hand spray equipment should be of the listed/approved type and be designed to be intrinsically safe and to not produce a spark of sufficient intensity to ignite vapor-air mixtures, nor result in appreciable shock hazard on encountering a grounded object.
  • The electrostatically charged, exposed elements of the spray gun should be designed so they can only be energized by the switch that also controls the paint supply.
  • The handle of the spray gun should be electrically connected to ground to prevent a buildup of static charge on the operator's body. Additionally, electrically-conductive objects in the spraying area, including paint containers and wash cans, should be adequately bonded and grounded and should be posted with warning signs indicating the necessity for grounding.
  • The electrostatic hand spraying equipment should be designed so the maximum surface temperature in the spraying area will not exceed 150°F (66°C) under any conditions.
  • The spraying area should be adequately ventilated to insure safe conditions.
  • The electrostatic apparatus should be equipped with automatic controls to disconnect the power supply to the high-voltage transformer and to signal the operator in the event of failure or stoppage of the ventilation equipment or occurrence of a ground between the high-voltage transformer and the spray gun.
  • Warning signs should be posted prohibiting smoking or the carrying of lighters, matches or other sources of ignition into the spraying area.
  • The electrical power supply should be disconnected and "locked out" before repair work is done on the electrostatic equipment.

See Chapter 11 of NFPA 33 for specific requirements for automatic electrostatic spray processes and Chapter 12 for handheld electrostatic spray processes.

Plural component systems

The use of chemically unstable chemicals, such as organic peroxides, in plural component systems requires, in addition to the controls for conventional spray processes, the following control measures:

  • The use of organic peroxides and other plural component coatings during spraying operations should be conducted in listed/approved spray booths.
  • To prevent the contamination of organic peroxide initiators with any foreign substance, extreme care should be exercised at all times in their handling and use.
  • Only spray guns and other related equipment, specifically manufactured for use with organic peroxides, should be used.
  • Separate pressure vessels and inserts that are specifically designed for the type of application should be used, both for the resin and for the organic peroxides. In no event, should these be interchanged.
  • Stainless steel, polyethylene, or other chemically non-reactive materials should be used for the construction of the organic peroxide pressure tank inserts.
  • Since the mixing of any dusts or overspray residues, which may result from the sanding or spraying of finished materials containing organic peroxides, with other materials may result in a spontaneous fire or explosion, extreme care should be exercised at all times.
  • All spilled peroxides should be promptly removed so that there are no residues remaining after the cleanup. The spilled materials should be removed by using a non-combustible absorbent and then promptly disposing of the absorbent.

Storage and handling of organic peroxides

Organic peroxides should be stored in a temperature-controlled, detached building, apart from all finished materials. Only the minimum daily requirements of organic peroxides should be brought to the processing area. Any material left over at the spraying station at the end of a day's operation should be disposed of carefully.

  • Organic peroxides should be kept away from all sources of heat, including steam pipes, radiators, open flames or sparks and solar radiation.
  • Extreme care should be exercised in the handling of organic peroxides to avoid any possibility of the occurrence of shock and friction, which can cause them to decompose and to react violently.
  • Organic peroxides should not be mixed directly with accelerators or promoters because this may result in a violent decomposition or explosion.
  • All smoking should be prohibited in the areas where organic peroxides may be present. "No Smoking" signs should be prominently displayed in these areas.
  • Only non-sparking tools should be used in any area where organic peroxides are stored, mixed or applied.
  • Only specifically trained personnel should be permitted to work with these materials.

See Chapter 16 of NFPA 33 for additional requirements for plural spray operations.

Powder coating systems

In addition to the risk control measures previously discussed for conventional spray processes, the following measures are specifically recommended for powder coating systems:

  • To prevent the accumulation of powder and to facilitate cleaning, the enclosures used for conducting coating operations should be completely enclosed, be of non-combustible construction with smooth surfaces, and be properly ventilated. All areas including horizontal surfaces, such as ledges, beams, pipes, hoods and booth floors, should be periodically cleaned to prevent the accumulation of powder. The surfaces should be cleaned with vacuum sweeping equipment of a type approved for use in hazardous locations. This will negate the scattering of the powder or the creation of powder clouds.
  • Coating operations may be conducted in adequately ventilated spray booths that are specifically designed to meet the requirements for enclosures in which combustible dust operations are conducted. Enclosed, adequately ventilated containers, such as tanks and bins constructed of non-combustible materials, can also be used for powder coating operations.
  • All metal parts of spray booths, exhaust ducts, and piping systems conveying aerated solids should be properly bonded and grounded, in accordance with the requirements of NFPA 77, Recommended Practice on Static Electricity, including powder transport, application and recovery equipment.
  • The temperature of the part being coated should never exceed the ignition temperature of the powder.
  • All enclosures of a powder coating operation, such as booths and recovery enclosures, which are effectively "tight" enclosures, should be provided with adequate explosion venting.
  • All non-deposited, air-suspended powders should be safely removed from the operation, via exhaust ducts, to a powder recovery system. The rate of exhaust should be based on the compositions, particle size, and density of the powders in use.
  • Automated powder coating operations should be provided with listed optical flame detection, installed and supervised in accordance with NFPA 72, National Fire Alarm and Signaling Code, which on flame detection will shut down the powder coating system, including the ventilation system, conveyers and power to the high-voltage elements in the spray area.
  • The exhausted air from the recovery system of a powder operation should not be used as recirculated or reconditioned air for the input air for that operation unless the particulate composition of the exhaust air has been returned to an acceptable safe level for that use.
  • All recirculating air systems should be equipped with a system that continuously monitors the exhausted air. These systems should be designed to signal the operator, as well as to shut down the operation, in the event the particle-removal equipment fails to maintain the air in the system below the acceptable safe level.

Electrostatic and fluidized powder coating The following are additional risk control measures for powder coating systems involving electrostatic fixed and handheld equipment and for fluidized beds:

  • Electric, hand-powder coating equipment should be designed not to produce a spark of sufficient intensity to ignite any powder-air mixtures likely to be encountered.
  • Electrostatic fluidized beds and associated equipment should be of approved types.
  • High-voltage circuits should be designed so that any discharge produced when the charging electrodes of the bed are approached, or contacted by a grounded object, is not of sufficient intensity to ignite any powder-air mixture likely to be encountered nor to result in an appreciable shock hazard.
  • The transformers, powder packs, control apparatus and all other electrical equipment, except for the charging electrodes and their connections to the power supply, should be located outside of the powder coating area (unless of a type specified by the NFPA 70 for use in hazardous operations).
  • All electrically-conductive objects within the powder coating area should be adequately bonded and grounded. In addition, the powder coating equipment should carry a prominent, permanently-installed warning regarding the necessity for grounding these objects.
  • All objects being coated should be maintained in electrical contact with the conveyor or other support equipment to ensure proper grounding. Hangers should be regularly cleaned to ensure effective contact, and areas of contact should not be composed of sharp points or knife-edges, wherever possible.
  • The electrical equipment should be interlocked with the ventilation system so that the equipment cannot be operated unless the ventilating fans are in operation.

See Chapter 115 of NFPA 33 for additional requirements for powder coating operations.

Drying processes

All drying and curing equipment used in conjunction with the spray application of flammable and combustible coatings should conform to the requirements of NFPA 86, Standard for Ovens and Furnaces, or Chapter 21 of the International Fire Code (IFC), published by the International Codes Council (ICC). Areas used for spraying operations should not be used alternately as a drying area if the arrangement will cause a substantial increase in the surface temperature of that area. The susceptibility to spontaneous heating and ignition of any overspray residue may be increased at temperatures above normal. Drying and curing heating systems that may have open flames or may produce sparks should not be installed in a spraying area. These systems may be installed next to the spray area if equipped with an interlocked ventilating system that is arranged to:

  • Thoroughly ventilate the drying area before the heating system can be started;
  • Maintain a safe atmosphere at any source of ignition;
  • Automatically shut down the heating system in the event of failure of the ventilating system.
  • Enclosed spray areas should be equipped with temperature monitoring and controls that will automatically shut off the drying apparatus if the air temperature in the spray area exceeds 200°F (93°C).

Automobile refinishing

Automobile-refinishing spray booths or enclosures, otherwise installed and maintained in full conformity with nationally recognized standards for spray booths and drying apparatus, may alternatively be used for drying with portable, electrical infrared-drying apparatus, but only when conforming with the following:

  • The interior of spray enclosures, especially the floors, is kept free of overspray deposits.
  • During drying operations, all drying apparatus and any electrical connections and wiring thereto is not located within the spray enclosure nor in any other location where spray residue may be deposited thereon.
  • Only equipment of a type approved for Class I, Division 2 locations is located within 18 in (45.7 cm) of the floor level.
  • All metallic parts of drying apparatus are properly bonded and grounded.
  • A warning sign is prominently located and permanently attached to the drying apparatus, indicating that the ventilation is maintained during the drying period and that spraying should not be conducted in the vicinity.
  • All spraying apparatus, drying apparatus, and ventilating system of spray enclosure is equipped with suitable interlocks arranged so that:
    1. Spray apparatus cannot be operated while drying apparatus is within the spray enclosure.
    2. The spray enclosure is purged of spray vapors for a period of not less than three minutes before drying apparatus can be energized.
    3. The ventilating system maintains a safe atmosphere within the enclosure during the drying process.
    4. The drying apparatus automatically shuts off in the event of failure of the ventilating system.

See Chapter 13 of NFPA 33 for additional requirements for drying and curing operations.

Frequently asked questions

This section provides answers to some commonly asked questions regarding paint spray and powder coating operations.

Sprayed materials questions

Often worksites have questions regarding what sprayed materials are subject to the requirements of NFPA 33. The following are some common materials related questions.

Does NFPA apply to the spray application of polyurethane products?

NFPA 33 applies to the spraying of flammable and combustible materials. In its liquid state, many formulations of polyurethane have a flash point between 100°F (37.8°C) and 140°F (60°C) and should be treated as a Class II combustible liquid. However, others may have flash points that are higher, and as such may not be considered combustible liquids. If the product your client is using falls within the definition of a flammable or combustible liquid, the standard states that "Spray application operations and processes shall be confined to spray booths, spray rooms, or spray areas, as defined in this standard."

How does NFPA 33 define flammable or combustible materials?

Subsection 3.3.11.1 of NFPA 33 defines a flammable or combustible material as "any material, including its residue, that is used in the spray application process, and also meets one of the following definitions, as given elsewhere in this section: (1) Flammable Liquid, (2) Combustible Liquid, (3) Combustible Powder."

See Client Handout CH-25-31, Flammable and Combustible Liquids - NFPA Classifications, for additional information.

Is a spray booth or enclosure necessary for powder coating, since this is not a conventional spray painting activity?

Yes. NFPA 33 applies to "spray application of flammable or combustible materials." Subchapter 3.3.11.1 of NFPA 33 includes combustible powders in the definition of flammable or combustible material. Thus, powdered coating is within the scope of the standard.

Is the application of adhesive using a spray gun subject to NFPA 33?

Chapter 1 of NFPA 33 provides a detailed list of the operations that are covered by the standard. The basic requirement is that the spray application is performed with flammable or combustible materials. Thus, the standard should be followed unless the customer is performing an excluded operation, which is listed in Chapter 1.1 of the standard.

Is the spray application of a water-based (latex) paint covered by NFPA 33?

NFPA 33 does not apply to operations using non-combustible materials. However, water-based (latex) paints may contain some amount of solvent, which can change the combustibility rating of the paint. Latex paints with flash points listed in the 200°F (93°C) range would meet the definition of a combustible liquid and be subject to NFPA 33. However, many latex paints do not have a flash point and are considered non-combustible. As such, the final determination of the applicability of NFPA 33, concerning a latex paint, should rely on the Safety Data Sheet (SDS) supplied by the paint manufacturer.

Construction questions

Often worksites have questions regarding the construction of spray areas, booths and rooms. The following are some common processes related questions.

An insured has constructed a spray booth from aluminum sheets and u-channel. Is it an acceptable construction technique?

The Occupational Safety and Health Association (OSHA) permits limited use of aluminum in spray booth construction. However, the NFPA 33 does not permit aluminum as a primary construction (i.e., structural) material. OSHA does permit (29CFR1910.107(b)(1)) aluminum to be used as a construction material in "intermittent or low volume spraying."

NFPA 33 limits the use of aluminum to ancillary components, such as work platforms or spray equipment. NFPA requires paint spray booths be separated from other operations by a one-hour firerated wall, floor, and ceiling assembly (or by distance). Because of the low melting point of aluminum, 1,220°F (606°C), a paint booth made of aluminum could not maintain structural stability during a fire event for one hour.

Are there electrical requirements for paint mixing rooms that mix flammable paints?

Yes. NFPA 33 provides requirements for paint mixing rooms in Section 8.3.3. Specifically, 8.3.3(7) states that "Mixing rooms shall be classified, for purposes of electrical area classification, the same as enclosed spray booths, in accordance with 6.5.4." Section 6.5.4 requires equipment inside the room be designed and listed for use in a Class I, Division 1 environment. Additionally, electrical equipment adjacent to openings in the mixing room should also be approved for such use in accordance with Section 6.5.4.

See Client Handout CH-25-22, Electrical Equipment - Hazardous Location Classification System, for additional information.

Do spray rooms and spray booths need to meet the same construction requirements?

No, not always. Chapter 5 of NFPA 33 provides the requirements for "spray areas, spray room and spray booth" construction. In many cases, all three share similar construction requirements, such as in the case of walls and ceilings. It is important to consider that the term "spray area" includes both spray rooms and spray booths, as well as non-enclosed spray areas.

Thus, in some cases, such as Section 5.1 of NFPA 33, the construction requirements will be the same and in other cases, it will differ greatly. Section 5.1 of NFPA 33 requires that walls, doors, and ceilings of a "spray area," which includes a spray booth, "be constructed of non-combustible or limited-combustible materials or assemblies and shall be securely and rigidly mounted or fastened. The interior surfaces of the spray area shall be smooth, designed and installed to prevent pockets that can trap residues, and designed to facilitate ventilation and cleaning."

While Section 5.1.6 requires spray rooms to be constructed with a one-hour fire-resistance rating, it does not have a requirement for spray booths. However, Section 5.3 provides that a spray booth can be either separated from other exposures by 3 ft. (0.9 m) or by a one-hour fire-rated floor/wall/ceiling assembly.

An insured wants to cut rectangular holes in his self-fabricated paint booth, cover them with Plexiglas, and put lights on the outside of the booth shining into the booth. Would that meet NFPA code for a spray booth in a woodworking shop?

The solution that the client wishes to use would be acceptable in part. NFPA 33 would allow the light fixture to be located outside the classified spray area and provide light via a clear protective panel, as noted in Section 6.6.1 of the standard. However, that section specifically states that "glass panels" need to meet the requirements of Section 5.4 of the standard.

Section 5.4.1 of the standard requires panels be made from "heat-treated glass, laminated glass, wired glass or hammered-wired glass and shall be sealed to confine vapors, mists, residues, dusts and deposits to the spray area." Section 5.4 also provides additional requirements for the installation, sealing, and maximum permitted surface temperature of these panels. Thus, the use of "Plexiglas" would not be within the scope of the code. There is an exception for listed spray booths that have other vision panels, not for modification of an existing booth. Additionally, Plexiglas may be much harder when removing spray residue from the glass, which would be counterproductive to providing adequate light for the work area.

Is carpeting an acceptable floor covering for an automotive paint spray booth or paint mixing room?

No. Most automotive spray paints are flammable or combustible. The use of an absorbent combustible material, such as carpeting, is not recommended for areas where flammable or combustible liquids may be spilled or in areas subject to overspray of these materials. Carpet may allow the buildup of flammable residue that when ignited will result in a rapidly developing fire. Additionally, materials, such as carpet, have a high potential for static charge generation. This charge generation and resulting discharge could act as an ignition source for flammable vapors.

Subsection 5.1.2 of NFPA 33 specifically requires the floor of spray areas be constructed of "non-combustible material, limited-combustible material, or combustible material that is completely covered by non-combustible material." Carpeting does not meet this requirement. Additionally, Subsection 8.3.3(1) provides that mixing areas should be constructed as outlined in Subsection 5.1. Thus, the presence of carpet would not be allowable under the standard.

Is it acceptable to put a damper in paint booth exhaust duct to prevent cold air from flowing back into the work area?

Yes. A damper can be installed in an exhaust duct. NFPA 33 requires exhaust ducts be designed and installed in accordance with NFPA 91, Standard for Exhaust Systems for Air Conveying of Vapors, Gases, Mists, and Noncombustible Particulate Solids. Placing a damper in the system is acceptable if the velocity to ensure adequate ventilation is maintained. NFPA 91 does provide an additional requirement in Section 4.5.5 as follows: "When dampers or louvers are used for weather or back-draft protection, they shall be located on the clean-air side of the filtration system." If the damper meets both conditions (velocity and clean-air side), it is permitted to prevent cold air while not compromising the paint booth's fire protection efforts. As always, only a qualified exhaust system installer should be permitted to modify the system that is in place.

Is there a maximum travel distance to a fire exit from any location within a paint booth used to spray flammable or combustible coatings?

Yes. A spray booth generally will require two exits. NFPA 33 requires spray booths be provided with means of egress that meet the requirements of NFPA 101, Life Safety Code. Subsection 7.11 of NFPA 101 provides the minimum egress requirements for high hazards areas, such as a paint spray booth. The subsection requires that the maximum travel distance to an exit not exceed 75 ft. (23 m). Additionally, at least two exits should be provided, unless all the following conditions are met:

  • Total floor space of the area does not exceed 200 ft.2 (18.6 m2).
  • The area is not occupied by more than three persons.
  • The maximum travel distance, within the area, to an exit door does not exceed 25 ft. (7.6 m).

Is there an NFPA requirement to provide ventilation for a paint mixing room, even when the paint is not heated to its flash point?

Chapter 8 of NFPA 33 contains requirements for paint mixing operations. This subchapter 8.3.3(5) specifies that paint mixing rooms be provided with a ventilation system producing at least one cubic foot per minute (cfm) of air movement per square foot (03.m3/m∙m2) of floor area, but not less than 150 cfm (4 m3/min).

Recently I saw a paint booth that had a plastic film applied to the walls that can be peeled away to remove overspray. Is this acceptable according to NFPA 33?

Yes. The covering you saw may be acceptable for use in a spray booth. NFPA 33 makes a provision for such a product in Section 10.2.2 of the standard. That section provides that "combustible coverings (thin paper, plastic) and strippable coatings shall be permitted to be used to facilitate cleaning operations in spray areas."

When a plastic covering is used, the section also requires that the covering "be of a static dissipative nature or shall have a maximum breakdown voltage of 4 kV to prevent accumulation of a hazardous static electric charge."

Fire and explosion questions

Often worksites have questions regarding the protection of spray areas, booths and rooms. The following are some common processes related questions:

Can a domestic water (i.e., drinking) system be used to supply an automatic sprinkler system protecting a small paint spray area?

Yes. NFPA 33 allows the use of a domestic water system to supply sprinklers that are only used for the protection of paint spray areas. Subsection 9.4.4 of NFPA 33 states, "Where sprinklers are installed to protect spray areas and mixing rooms only, water shall be permitted to be supplied from domestic water systems, provided the domestic supply can meet the demand for the design criteria of 9.4.2."

Does a continuous, combustible-powder spray enclosure, such as an automated spray tunnel, need to be protected in the same manner as a wet spray paint booth?

Yes. Chapter 9 of NFPA 33 requires that flammable and combustible spray operations be protected by an automatic fire protection system. Subsection 9.2 provides the fire prevention requirements for these operations, and references Subsection 9.7, which provides protection requirements for automated powder application equipment. Additional information supporting the requirements for protecting these areas is provided in Appendix A9.7 of NFPA 33.

In addition, NFPA 72, National Fire Alarm Code, requires that the equipment be provided with optical flame detection. These requirements are intended to ensure that a fire developing inside a spray tunnel will be efficiently controlled. In the absence of automatic detection, a fire in the tunnel could grow until it involved the structure of the tunnel, resulting in a fire too large for the area sprinkler system to control.

Does NFPA provide a thickness requirement for the "thin paper bags" that are used to protect sprinkler heads from overspray in paint booths?

NFPA 13, Standard for the Installation of Sprinkler Systems, does not provide a thickness requirement for the "thin paper bags" used to cover sprinkler heads. Paper bags do not shrink, which will cause them to encase the head, and as such do not have a thickness provided. However, when cellophane (i.e., plastic) bags are used, their thickness should not exceed 0.003 in (0.076 mm), which is slightly more than typical plastic "sandwich" bag. Plastic baggies, used to protect sprinkler heads, have a thickness specification to ensure that when heated the plastic will shrink and break. If a bag of a heavier thickness is used, it could, when heated, shrink and encase the head. This could prevent the head from operating. However, in both cases, it is critical that the bags be changed as soon as a residue begins to build up on them.

Does NFPA require an automatic sprinkler system, or any other form of fire suppression, in a powder coating booth where the operators stand in the booth and use a handheld sprayer?

If the operator is spraying a flammable or combustible material, then NFPA 33 would apply. Chapter 9 of NFPA 33 requires that spray areas be protected with an approved automatic fire protection system. No exceptions are provided in NFPA 33 for areas that have an operator present during the application process.

Some property owners may argue that the operator is present and that, if a fire occurred, the operator would use a portable extinguisher to extinguish it. However, this scenario does not address the risk of a fire occurring after the operator has left the paint booth, but flammable materials are still present in the air, or any off-gassing from drying operations, and the absence of automatic fire protection.

Does the exhaust duct of a spray room used exclusively for open spraying of flammable or combustible materials need to be protected by a fire protection system?

Yes. It does require protection. Chapter 9 of NFPA 33 provides the requirements for protection of spray applications. Section 9.1 states that "spray areas, which include by definition any associated exhaust plenums and exhaust ductwork, any particulate filters, any solvent concentrator units, any recirculation air supply units, and mixing rooms, shall be protected with an approved automatic fire protection system." As such, the exhaust system for the spray booth you described also requires automatic protection, such as one of the following:

  • An automatic water sprinkler system
  • An automatic foam water sprinkler system
  • A carbon dioxide extinguishing system
  • A dry chemical extinguishing system
  • A gaseous agent extinguishing system

Extinguishing systems should be installed and maintained in accordance with the applicable NFPA standard for the system in use.

Processes questions

Often worksites have questions regarding what controls apply to specific spray processes. The following are some common processes related questions:

Are incidental spray painting operations with aerosol spray cans covered by NFPA 33?

No. NFPA 33 does not address incidental spraying operations using aerosols. Subsection 1.1.5 of NFPA 33 provides that the standard does not apply to "small portable spraying equipment or aerosol products that are not used repeatedly in the same location." Further, Annex A1.1.5 provides that "occasional" use of this equipment "is not likely to result in hazardous accumulations of overspray" and thus not covered by the standard.

While incidental spraying is not covered by NFPA 33, there are several common control measures that should be followed for all spraying applications, including:

  • Electrical equipment and wiring located in spray areas should be designed, installed, and approved in accordance with the provisions of NFPA 70 for use in Class I, Division I, Group D classified locations.
  • Mechanical ventilation should be provided for all spraying areas to remove flammable vapors, mists or powders.
  • The paint spraying equipment and the ventilation system should be properly maintained.
  • All paint spraying and surrounding areas should be kept free of the accumulation of deposits of combustible residues.

Can an open floor area be used for spraying flammable finishes? Is there a distance from an open floor spraying area from which classified electrical equipment should be used?

Yes. An open floor area can be used for the spray application of flammable materials. NFPA 33 requires spray applications of flammable materials be conducted in "spray booths, spray rooms, or spray areas." NFPA 33 defines a spray area in Subsection 3.3.2.3 as: "Any fully enclosed, partly enclosed or unenclosed area in which dangerous quantities of flammable or combustible vapors, mists, residues, dusts or deposits are present due to the operation of spray processes…"

The area is subject to the electrical requirements of Chapter 6 which states that electrical wiring and equipment that is in the spray area should be listed for the hazard present (e.g., Class I, Division 1, etc.). Additionally, electrical wiring and equipment that is within the 20 ft. (6.1 m) horizontally and 10 ft. (3 m) vertically of an unenclosed (i.e., open floor) spray area, and not separated from the spray area by partitions, should be listed for the next lowest classification, based on the hazard present (e.g., Class I, Division 2, etc.).

Does the NFPA require routine paint spraying operations, with flammable materials, to be performed inside a spray booth or under a spray hood?

NFPA 33 requires indoor spray applications of flammable materials be conducted in "spray booths, spray rooms, or spray areas." Chapter 3.3.2.3 of NFPA 33 defines a spray area as "Any fully enclosed, partly enclosed or unenclosed area in which dangerous quantities of flammable or combustible vapors, mists, residues, dusts or deposits are present due to the operation of spray processes..." From a design standpoint, spray areas should meet the requirements of Chapter 5, such as 5.1, Walls and Ceilings, and the electrical requirements of Chapter 6. Additionally, spray areas are required to meet the ventilation and fire protection provided in NFPA 33.

Does the NFPA 33 require spark detection for manual powder coating processes?

No. While NFPA 33 does apply to manual powder coating processes, Chapter 9 only requires spark detection for automated spray processes.

Is cleaning of a spray gun with a solvent subject to NFPA 33?

If the cleaning process includes spraying liquid through the gun, then the cleaning operation would be subject to NFPA 33.

Is the application of spray-on bed liner materials exempt from the requirements of NFPA 33?

Section 14.1.1 of NFPA 33 provides an exemption for spray-on bed liner operations that are performed with adequate ventilation and when the requirements of 14.1.1.1 through 14.1.1.4 are met. The subsections require the following when spraying:

  • No flames or spark-producing equipment may be located within 20 ft (61 m).
  • No drying or curing equipment may be operated within 20 ft. (61 m).
  • Solvent used in the area may not have a flash point less than 100°F (37.8°C).

The sprayed material (or subcomponent) may not have a flash point less than 100°F (37.8°C); must be classified as a Class IIIB liquid and may not include any organic peroxide catalyst; and must be "no more hazardous than UL Class 30-40, when tested in accordance with ANSI/UL 340, Test for Comparative Flammability of Liquids," published by Underwriters Laboratories (UL).

It is important to consider that ventilation is defined by Section 3.3.16 of NFPA 33 as follows: "For the purposes of this standard, movement of air that is provided for the prevention of fire and explosion and is sufficient to prevent accumulation of vapor–air mixtures in concentrations over 25 percent of the lower flammable limit." As such, the air movement system for the spray area should be evaluated to ensure it meets the requirements of NFPA 33.

What is a flash-off area, and how does it relate to spray painting?

NFPA 33 defines a flash-off area as "an open or enclosed area after a spray application process where vapors are released due to exposure to ambient air or a heated atmosphere." In short, if a coated product releases flammable or combustible vapors during the drying process, the area that it is in would meet the definition of a flash-off area. The concern is that volatile vapors could accumulate in an area if proper ventilation is not provided, and these vapors could ignite if an ignition source were present. Chapter 13 of NFPA 33 provides the requirements for drying and curing areas. Subchapter 13.4 provides the specific requirements for flash-off areas, including electrical equipment classifications, ventilation, and fire protection requirements.

What are the general requirements for storing cans of spray paint? We are looking at a limited quantity in a supply warehouse setting.

The type of storage arrangement will depend upon the degree of fire hazard posed by the spray paint. Spray paint is typically classified as a Level 3 aerosol product. Aerosol products are classified by NFPA 30B, Code for the Manufacture and Storage of Aerosol Products, published by the National Fire Protection Association (NFPA), based on their heat release rate during combustion. Level 1 aerosols have a heat release rate of less than 8,600 Btu/lb. (20 kJ/g); Level 2 aerosols have a heat release rate of more than 8,600 Btu/lb. (20 kJ/g) and less than 13,000 Btu/lb (30 kJ/g); and Level 3 aerosols have a heat release rate of more than 13,000 Btu/lb (30 kJ/g). Aerosols, as well as other combustible materials, should be stored according to NFPA 230, Fire Protection of Storage. For Level 1 aerosols, while there are no quantity restrictions, storage areas should be inspected regularly to make sure aisles are clear and products are stored according to good practices.

Storage areas for Level 2 and 3 aerosols should be separated from retail display areas by fire-resistive construction. Other requirements for the storage of Level 2 and 3 aerosols include:
  • The maximum weight, in sprinklered buildings, should not exceed 2,500 lb./ft.2 (1135 kg/m2) for a ground level sale's floor and 500 lb./ft.2 (227 kg/m2) for upper floors of buildings;
  • No more than 1,000 lbs. (454 kg) may be displayed per 10-ft. x 10-ft. (3-m x 3-m) area; and
  • Storage should be a minimum of 25 ft. (7.6 m) from any flammable or combustible liquids when the storage height exceeds 8 ft. (2.4 m).

See Fire Protection Report FP-70-14, Aerosol Product Storage, for additional information on this topic.

References

  1. Engineering and Safety Service. Static Electricity. FP-70-08. Jersey City, NJ: ISO Services, Inc., 2016.
  2. ---. Storage of Flammable and Combustible Liquids in Containers. FP-70-12. Jersey City, NJ: ISO Services, Inc., 2014.
  3. International Codes Council (ICC). International Fire Code. 2015 ed. Falls Church, VA: ICC, 2015.
  4. National Fire Protection Association (NFPA). Fire Protection Handbook. 20th ed. Quincy, MA: NFPA, 2008.
  5. ---. National Electrical Code. NFPA 70. Quincy, MA: NFPA, 2017.
  6. ---. Recommended Practice for Electrical Equipment Maintenance. NFPA 70B. Quincy, MA: NFPA, 2016.
  7. ---. Standard for the Installation of Sprinkler Systems. NFPA 13. Quincy, MA: NFPA, 2016.
  8. ---. Uniform Fire Code. NFPA 1. Quincy, MA: NFPA, 2015.

COPYRIGHT ©2017, ISO Services, Inc.

To learn more about Hanover Risk Solutions, visit hanoverrisksolutions.com


The recommendation(s), advice and contents of this material are provided for informational purposes only and do not purport to address every possible legal obligation, hazard, code violation, loss potential or exception to good practice. The Hanover Insurance Company and its affiliates and subsidiaries ("The Hanover") specifically disclaim any warranty or representation that acceptance of any recommendations or advice contained herein will make any premises, property or operation safe or in compliance with any law or regulation. Under no circumstances should this material or your acceptance of any recommendations or advice contained herein be construed as establishing the existence or availability of any insurance coverage with The Hanover. By providing this information to you, The Hanover does not assume (and specifically disclaims) any duty, undertaking or responsibility to you. The decision to accept or implement any recommendation(s) or advice contained in this material must be made by you.

LC DEC 2018 2015-345
171-1747 (04/18)


This site uses cookies. View our privacy policy and online privacy statement.

California residents: View the information we collect and how we use it.

×