Electrical distribution system
Visual Observations | Equipment | Definition | Observations |
Cables and bus | Distributes electrical power throughout a building, connecting various components of an electrical distribution system. |
No sharp bends |
|
Switchgear | Combination of electrical disconnect switches, fuses or circuit breakers used to control, protect and isolate electrical equipment. Switchgear is used both to deenergize equipment to allow work to be done and to clear faults downstream. |
Covers in place |
|
Circuit breakers | Controlling power to a circuit as well as providing protection to equipment in that circuit by interrupting fault conditions. |
Enclosed |
|
Transformers | Device that transfers electric energy from one alternating current circuit to one or more other circuits, either increasing (stepping up) or reducing (stepping down) the voltage. |
Open and accessible |
Operation and maintenance | Keep it ____________ | ||
Read and follow all manufacturers' guidelines and instructions for periodic service, maintenance and inspection of equipment and systems. Caution— Always de-energize electrical equipment before testing, cleaning or performing maintenance. |
COOL | All vent and air circulation openings must be clear and operational. |
|
CLEAN | Dust and/or dirt accumulations should be removed from the equipment and surroundings. Space in switchrooms and switchgear enclosures should not be used for storing tools, supplies or other material. | ||
DRY | Precaution should be taken to prevent steam, chemicals, moisture or condensation from entering electrical enclosures. | ||
TIGHT | Clean and tighten all loose parts and replace any that are worn. Equipment should be manually exercised to establish that moving parts do not bind and are free to operate. |
Electrical testing | Equipment | Testing | Frequency |
Testing frequency guidelines should be tempered by the size of the equipment, the location of the equipment, the frequency of operation and the criticality it represents. |
Cables and bus | Infrared thermography |
Annually 3 years |
Switchgear | Infrared thermography |
Annually 3 years 3 years |
|
Circuit breakers | Infrared thermography |
Annually 3 years 3 years |
|
Transformers | Infrared thermography |
Annually Annually 5 years |
|
In addition: |
Insulation resistance test Dissolved gas analysis, oil screen tests |
3 years Yearly |
Download and print this document.
To learn more about Hanover Risk Solutions, visit hanoverrisksolutions.com
© Copyright 2013 The Hartford Steam Boiler Inspection and Insurance Company. All Rights Reserved. Used with permission of The Hartford Steam Boiler Inspection and Insurance Company.
The recommendation(s), advice and contents of this material are provided for informational purposes only and do not purport to address every possible legal obligation, hazard, code violation, loss potential or exception to good practice. The Hanover Insurance Company and its affiliates and subsidiaries ("The Hanover") specifically disclaim any warranty or representation that acceptance of any recommendations or advice contained herein will make any premises, property or operation safe or in compliance with any law or regulation. Under no circumstances should this material or your acceptance of any recommendations or advice contained herein be construed as establishing the existence or availability of any insurance coverage with The Hanover. By providing this information to you, The Hanover does not assume (and specifically disclaims) any duty, undertaking or responsibility to you. The decision to accept or implement any recommendation(s) or advice contained in this material must be made by you.
LC MAR 2019 13-349
171-1084 (3/14)