The Hanover Insurance Group

Electrical distribution system

Visual Observations Equipment Definition Observations
Cables Cables and bus

Distributes electrical power throughout a building, connecting various components of an electrical distribution system.

No sharp bends
No physical damage
No signs of heat
No temporary wiring
Free of moisture and oil

Switchgear Switchgear

Combination of electrical disconnect switches, fuses or circuit breakers used to control, protect and isolate electrical equipment. Switchgear is used both to deenergize equipment to allow work to be done and to clear faults downstream.

Covers in place
Labeled
Accessible
No signs of water
Vent openings clear

Circuit breaker Circuit breakers

Controlling power to a circuit as well as providing protection to equipment in that circuit by interrupting fault conditions.

Enclosed
Labeled
Accessible
No physical damage
No signs of heat
No signs of distress
No missing knockouts

Transformers Transformers

Device that transfers electric energy from one alternating current circuit to one or more other circuits, either increasing (stepping up) or reducing (stepping down) the voltage.

Open and accessible
No dirt accumulations
No physical damage
No signs of overheating
No leakage (oil filled)
Adequately protected



Operation and maintenance Keep it ____________

Read and follow all manufacturers' guidelines and instructions for periodic service, maintenance and inspection of equipment and systems.



Caution— Always de-energize electrical equipment before testing, cleaning or performing maintenance.

COOL

All vent and air circulation openings must be clear and operational.
Installed filters should be cleaned or replaced. It is important to prevent excessive heat buildup in electrical enclosures and equipment rooms.

CLEAN Dust and/or dirt accumulations should be removed from the equipment and surroundings. Space in switchrooms and switchgear enclosures should not be used for storing tools, supplies or other material.
DRY Precaution should be taken to prevent steam, chemicals, moisture or condensation from entering electrical enclosures.
TIGHT

Clean and tighten all loose parts and replace any that are worn. Equipment should be manually exercised to establish that moving parts do not bind and are free to operate.



Electrical testing Equipment Testing Frequency

Testing frequency guidelines should be tempered by the size of the equipment, the location of the equipment, the frequency of operation and the criticality it represents.

Cables and bus

Infrared thermography    
Visual inspect/clean/adjust                            

Annually
3 years
Switchgear

Infrared thermography
Visual inspect/clean/adjust                                
Contact resistance test                                    

Annually
3 years
3 years
Circuit breakers

Infrared thermography
Visual inspect/clean/adjust
Contact resistance, breaker trip, relay calibration

Annually
3 years
3 years
Transformers

Infrared thermography
Visual inspect-
Power factor, turns ratio


Annually
Annually
5 years

In addition:
Dry-type
Power & distribution


Insulation resistance test
Dissolved gas analysis, oil screen tests

3 years
Yearly
For a more detailed description on electrical maintenance and testing, consult Standard for an Electrical Preventive Maintenance (EPM) Program.

Download and print this document.

To learn more about Hanover Risk Solutions, visit hanoverrisksolutions.com


© Copyright 2013 The Hartford Steam Boiler Inspection and Insurance Company. All Rights Reserved. Used with permission of The Hartford Steam Boiler Inspection and Insurance Company.

The recommendation(s), advice and contents of this material are provided for informational purposes only and do not purport to address every possible legal obligation, hazard, code violation, loss potential or exception to good practice. The Hanover Insurance Company and its affiliates and subsidiaries ("The Hanover") specifically disclaim any warranty or representation that acceptance of any recommendations or advice contained herein will make any premises, property or operation safe or in compliance with any law or regulation. Under no circumstances should this material or your acceptance of any recommendations or advice contained herein be construed as establishing the existence or availability of any insurance coverage with The Hanover. By providing this information to you, The Hanover does not assume (and specifically disclaims) any duty, undertaking or responsibility to you. The decision to accept or implement any recommendation(s) or advice contained in this material must be made by you.

LC MAR 2019 13-349
171-1084 (3/14)


This site uses cookies. View our privacy policy and online privacy statement.

California residents: View the information we collect and how we use it.

×